Floor job on an Australian Japanese-import Toyota Hiace KDH201 (Regius Ace fridge van) with a DENSO Aeon fridge / freezer (CGA 138, R134a). Panel showed F4 (cooling fuse 2). Evaporator fan motor was OK when powered directly — the open path was in the fuse / command side, not a dead motor.
What we checked
- Dedicated fridge fuse box cover C8639-44010 under the dash
- Cooling 20A and related condenser fuses on that cover
- Meter shade 5A — control panel feed (LC1 if dead)
- Inline COOLER 15A under the driver’s dash (easy to miss)
- DENSO Aeon panel codes F3 / F4 = cooling fuse 1 / 2
Why the English manual
Public Japanese owner books name the fuses but are hard to use on the floor here. There is no clean Hiace-specific English fridge fuse book online for this import. We re-authored an English workshop pack from the DENSO Aeon manual plus this van’s photos and fuse finding so another workshop can follow the same path.
Download the English workshop manual (PDF)
Full re-authored English pack for this vehicle: DENSO Aeon safety and operation pages, fault / fuse notes (F3, F4, LC1), Japanese fuse table with English translation beside it, and this-van photos.
Download PDF — Hiace KDH201 / DENSO Aeon workshop manual
Direct link: /assets/downloads/Toyota-Hiace-KDH201-Regius-Ace-DENSO-Aeon-Fridge-Workshop-Manual.pdf